NAZJ6 DC System Earth Fault Detector NAZJ6直流系統(tǒng)接地故障測(cè)試儀
產(chǎn)品簡介
NAZJ6直流系統(tǒng)接地故障測(cè)試儀是新一代直流接地故障測(cè)試儀。NAZJ6便攜式直流系統(tǒng)接地故障測(cè)試儀,是我公司自成立以來開發(fā)出的直流系統(tǒng)接地故障測(cè)試儀升級(jí)換代產(chǎn)品,該系列產(chǎn)品已在現(xiàn)場的大量應(yīng)用中獲得極大的好評(píng),已經(jīng)成為國內(nèi)**的產(chǎn)品,廣泛應(yīng)用于外多個(gè)市場。本裝置以系統(tǒng)安全為前提,按行業(yè)標(biāo)準(zhǔn)的*要求,以可靠的低頻信號(hào)方式進(jìn)行檢測(cè),并在現(xiàn)場進(jìn)行了大量的實(shí)際應(yīng)用,對(duì)系統(tǒng)無任何影響。它能夠適用于任何電壓等級(jí)的直流系統(tǒng),配備了高精度的檢測(cè)鉗表,通過對(duì)多種信號(hào)的高效處理大大提高了檢測(cè)范圍與抗干擾能力;采用了*的算法和*的模糊控制計(jì)算理論,將被檢測(cè)絕緣支路的優(yōu)勢(shì)程度以數(shù)值的形式表示出來,充分體現(xiàn)了人工智能的優(yōu)越性;對(duì)于接地點(diǎn)位置的斷定,它們更是擁有準(zhǔn)確的判斷力,每次檢測(cè)都能夠指出接地點(diǎn)位置及方向。
NAZJ6直流系統(tǒng)接地故障測(cè)試儀以系統(tǒng)安全為前提,按行業(yè)標(biāo)準(zhǔn)的*要求,以可靠的低頻信號(hào)方式進(jìn)行檢測(cè),并在現(xiàn)場進(jìn)行了大量的實(shí)際應(yīng)用,對(duì)系統(tǒng)無任何影響。
發(fā)電廠、變電站的直流系統(tǒng)為控制、保護(hù)、信號(hào)和自動(dòng)裝置提供電源,直流系統(tǒng)的安全連續(xù)運(yùn)行對(duì)保證發(fā)供電有著極大的重要性。由于直流系統(tǒng)為浮空制的不接地系統(tǒng),如果發(fā)生兩點(diǎn)接地,就可能引起上述裝置誤動(dòng)、拒動(dòng),從而造成重大事故。因此當(dāng)發(fā)生一點(diǎn)接地時(shí),就應(yīng)在保證直流系統(tǒng)正常供電的同時(shí)準(zhǔn)確迅速地探測(cè)出接地點(diǎn),排除接地故障,從而避免兩點(diǎn)接地可能帶來的危害。
NAZJ6直流系統(tǒng)接地故障測(cè)試儀用于在不斷電情況下查找發(fā)電廠、變電站直流系統(tǒng)接地點(diǎn)的準(zhǔn)確位置。各種類型的接地故障,均能迅速地查找出接地點(diǎn),準(zhǔn)確率達(dá)到100%。
產(chǎn)品別名
直流系統(tǒng)接地故障測(cè)試儀,直流接地故障測(cè)試儀,直流系統(tǒng)故障綜合測(cè)試儀
產(chǎn)品特性
1、使用簡單。NAZJ6直流系統(tǒng)接地故障測(cè)試儀只需打開電源開關(guān)就可直接使用,無需別的按鍵操作。
2、安全可靠。NAZJ6直流系統(tǒng)接地故障測(cè)試儀無需停浮充電機(jī)及其它一切電源,對(duì)直流系統(tǒng)沒有任何影響。
3、適用電壓等級(jí)多。直流系統(tǒng)220V、110V、48V、24V都可以使用。
4、適用范圍廣。任何類型電廠、變電站、煤礦、化工廠等供電部門都可使用。
5、攜帶方便,信號(hào)接收器自帶電池,無需外接電源,可以隨身攜帶到任何地方查找接地點(diǎn)。
6、直流系統(tǒng)不斷電查找接地點(diǎn),不影響系統(tǒng)正常工作。
7、抗干擾能力強(qiáng),克服了系統(tǒng)分布電容的影響。
8、智能化充電管理,減少充電時(shí)間,延長電池壽命。
Product introduction
NAZJ6 DC System Earth Fault Detector applies to all DC system in any voltage ,equipped with high-precision tester ,expanded the tested range and strengthened the anti-interference ability by processing many kinds of signal. Adopted excellent method of calculation and advanced Fuzzy control calculation theory ,show us the advancement of the measured circuit branch by numerical value, which reflect the superiority of artificial intelligence sufficiently. Correctly detect the position of the earthing contact each time.
Also called name
Earth fault detector, DC system earth fault detector
The Characteristics of the products
1. Easy to use, customers can directly operate only need turn on the power switch.
2. Safe and reliable, do not need power off the charger or other power source, without effects to DC system.
3. Applies to various voltage , DC system 220V, 110V, 48V, 24V.
4. Wide range of application, any power plant, transformer substation, colliery, chemical plant and others power supply departments.
5.Easy to carry, the signal receiver equipped with battery, do not need external power source.
6.DC system do not need power off when searching the earthing contact, do not affect the normal work of the system.
7. Strong anti-jamming ability, without the effects by system distributed capacitance.
8.Intelligent charge Management, shorten the charging time, lengthen the battery life.
The parameters of the products
1, The signal generator
◆output signal frequency: 2.5Hz
◆ Signal-load output voltage: ± 20V ± 5%
◆ signal voltage amplitude error: <5%
◆ signal Short circuit output current: ≤ 80mA
◆ output impact resistance: 400V DC shock
◆ Power supply voltage: AC220V ± 10%
◆ voltage frequency: 50Hz ± 5%
◆ Input fuse: 200mA
◆ Maximum power: 3W
◆ Volume: 300mm × 270mm × 200mm
2, The signal receiver
◆ signal current detection sensitivity: 0.5mA
◆ signal generator impedanceW: 40K
◆ Maximum output current: 2.5 mA
◆ Receiver Display: Digital 0-19
◆ Volume: 210mm × 100mm × 32mm
A jaw size: Φ50mm
B jaw size: Φ7mm × 9mm
3, The entire machine
◆ detecting the maximum ground resistance: 300KΩ
◆ detect maximum capacitance: 20μF
◆ earth resistance measurement accuracy :0-4 .5 KΩ error ≤ 0.5KΩ
◆Grounding capacitance measurement range:3-60uF
◆Grounding capacitance measurement accuracy: 3-10uF error≤1uF
Product precautions information
1 The unit is must carefully handled when transportation, operation and storage, fall or strong vibration, etc. is not allowed.
2. Signal source shall be added to the bus fault and ground.
3. The calipers of NAZJ6 DC System Earth Fault Detector only work for AC circuit, not DC circuit.
4 When all branches have no grounding, should pay attention to whether the power supply part of the grounding point, such as batteries, chargers and other parts.
5 The battery life can be extend if turn off the clamp and the signal receiver when not in use during the detection process.
6 Replace the battery when signal receiver power is low.
7 In order to keep the accuracy, do not hold clamp using your hand durning the detection process, should be allowed to clamp in a quiescent state.